| Date |
Text |
| 2023-06-01 14:57:54 | ROOF OVER BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23040249 |
| | 3114 45TH ST |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- PROVIDE ENGINEERING ANALYSIS SHOWING THAT EXISTING |
| | STRUCTURE IS ADEQUATE TO RECEIVE THE ADDITIONAL ROOF |
| | RUGGER RETROFIT FRAMING SYSTEM. |
| | SEC. 706.2 FBC-EXISTING BUILDING. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | 2- ENGINEER OF RECORD FOR THE SITE SPECIFIC |
| | INSTALLATION OF THE ROOF RUGGER RETROFIT FRAMING SYSTEM |
| | TO REVISE PLANS AND CALCULATIONS. THE ULTIMATE WIND |
| | SPEED ADOPTED BY THE CITY OF WEST PALM BEACH IS 170MPH |
| | NOT 168 MPH. SEC. 120 CITY AMENDMENTS. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | INSTALLATION OF THE HIGH AND LOW EAVE TRIMS SHOWN ON |
| | PLANS. SPECIFY ALL FASTENERS. SEC. 1609.1 FBC-BUILDING. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR NEW ROOF PANELS. |
| | NOTE: CLEARLY IDENTIFY PANEL FASTENING FOR ALL ROOF |
| | ZONES. |
| | |
| | 5- ENGINEER OF RECORD FOR THE SITE SPECIFIC |
| | INSTALLATION OF THE ROOF RUGGER RETROFIT FRAMING SYSTEM |
| | TO REVIEW AND APPROVE IN WRITING (NOT SIGNING AND |
| | SEALING) ABOVE PRODUCT APPROVAL AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: CLEARLY IDENTIFY PANEL FASTENING FOR AL ROOF |
| | ZONES. |
| | |
| | 6- DRAWINGS S1, S2 AND S3 AND CORRESPONDING |
| | CALCUALTIONS: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. . THE TEXT BOX LANGUAGE MUST BE |
| | IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR |
| | G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/... |
| | AND REVISE AS REQUIRED. |
| | |
| | SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |