| Plan Review Notes For Permit 23040243 |
| Permit Number |
23040243 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-13 12:07:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF "INSTALL VINYL PLANKING", | | | HOWEVER, THERE IS NO SPEC SHEET NOR A PRODUCT NAME FOR | | | THE ACTUAL PROPOSED VINYL FLOORING. | | | | | | VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT | | | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL | | | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING | | | THE FIRE BEHAVIOR RATING. | | | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | | WOULD NOT BE REQUIRED. | | | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|