| Plan Review Notes For Permit 23040208 |
| Permit Number |
23040208 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-10 14:14:04 | | | | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23040208 | | | 4/10/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE GAS RISER IS INCOMPLETE: | | | A) SHOW THE MAIN SUPPLY PIPE SIZE FROM THE METER TO THE | | | PE RISER- SEC. G2413.3 FBC RES. | | | B) SHOW THE TYPES OF BRANCH PIPING TO THE APPLIANCE | | | INCLUDING PIPE SIZES AND PIPE RUN LENGTHS- SEC. | | | G2413.3. | | | C) LABEL THE POOL HEATER AS FUTURE- UNDER SEPARATE | | | PERMIT. THE POOL HEATER CAN BE INCLUDED WITH THIS GAS | | | PERMIT IF THE COST OF THE UNIT IS ADDED INTO THE PERMIT | | | VALUE- SEC. 109.3 WPB. | | | D) THE APPROVED GAS RISER UNDER PERMIT 21080543 SHOWED | | | A GAS LINE TO A FUTURE GENERATOR. PLEASE SHOW THE | | | BRANCH LINE AND GAS TIGHT CAP- SEC. G2415.15. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|