2023-04-10 14:14:04 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23040208
 4/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER IS INCOMPLETE:
 A) SHOW THE MAIN SUPPLY PIPE SIZE FROM THE METER TO THE
 PE RISER- SEC. G2413.3 FBC RES.
 B) SHOW THE TYPES OF BRANCH PIPING TO THE APPLIANCE
 INCLUDING PIPE SIZES AND PIPE RUN LENGTHS- SEC.
 G2413.3.
 C) LABEL THE POOL HEATER AS FUTURE- UNDER SEPARATE
 PERMIT. THE POOL HEATER CAN BE INCLUDED WITH THIS GAS
 PERMIT IF THE COST OF THE UNIT IS ADDED INTO THE PERMIT
 VALUE- SEC. 109.3 WPB.
 D) THE APPROVED GAS RISER UNDER PERMIT 21080543 SHOWED
 A GAS LINE TO A FUTURE GENERATOR. PLEASE SHOW THE
 BRANCH LINE AND GAS TIGHT CAP- SEC. G2415.15.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  