| 2023-06-29 12:21:54 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23040149 |
| | 6/28/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. BASED ON THE RECENT CODE |
| | VIOLATIONS STOP WORK ORDER AND JOBSITE PHOTOS DATED |
| | 6-6-23 NEW BATHROOMS AND PLUMBING HAVE BEEN INSTALLED |
| | IN THE TENANT SPACE WITHOUT A WPB BUILDING DEPARTMENT |
| | PERMIT AND PLAN REVIEW. PLEASE PROVIDE PLUMBING PLANS |
| | FOR THE BUILDOUT IN COMPLIANCE WITH SECS. 107.2.1 & |
| | 107.3.5.1.3 WPB. THE PLANS SHALL INCLUDE THE FOLLOWING |
| | ITEMS 1-8. |
| | |
| | 1) PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE WITH THE |
| | APPROPRIATE OCCUPANCY CLASSIFICATION AS LISTED IN TABLE |
| | 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED |
| | AND PROVIDED NUMBER OF PLUMBING FIXTURES. |
| | |
| | 2) PLUMBING FLOOR PLAN DRAWINGS SHOWING PLUMBING |
| | FIXTURE AND APPLIANCE LOCATIONS AND PIPING RUNS THROUGH |
| | THE TENANT SPACE INCLUDING PIPES RUN UNDERSLAB AND |
| | ABOVE CEILINGS- SECS. 604 & 704-711 FBC P. |
| | |
| | 3) SANITARY DRAINAGE AND WATER RISER DRAWINGS- SEC 604 |
| | & 704-711 FBC P. |
| | |
| | 4) PLUMBING FIXTURE SCHEDULE- SECS. 404- 422 FBC P. |
| | |
| | 5) LOCATION OF THE WATER HEATER OR OTHER SOURCE OF HOT |
| | WATER SUPPLY FOR CULINARY, CLEANSING, LAUNDRY, OR |
| | BUILDING MAINTENANCE PURPOSES- SEC. 607.1 FBC P. |
| | |
| | 6) TEMPERATURE LIMITING MEANS AT THE HOT WATER SOURCE |
| | AND AT PUBLIC LAVATORIES- SEC. 607.1.1 & 607.1.2 FBC P. |
| | |
| | 7) THE SCOPE OF FOOD PREP OR COOKING OPERATIONS TO BE |
| | CONDUCTED IN THE SPACE AND PROVIDE A FOOD PREP |
| | EQUIPMENT PLAN AND SCHEDULE IF APPLICABLE. PLEASE NOTE |
| | GREASE WASTE INTERCEPTOR SPECIFICATIONS, CALCULATIONS |
| | AND GREASE WASTE PIPING DRAWINGS ARE REQUIRED FOR |
| | REMOVAL OF GREASE LADEN WASTE DISCHARGING FROM PLUMBING |
| | FIXTURES AS A RESULT OF FOOD PREP, COOKING AND |
| | WAREWASHING OPERATIONS IN THE SPACE- SEC. 1003.3.1 FBC |
| | P. PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE INTERCEPTOR BUT PLANS ARE ALSO |
| | REQUIRED UNDER THE MASTER PERMIT. |
| | |
| | 8) ENLARGED BATHROOM FLOOR PLAN DRAWINGS SHOWING THE |
| | FOLLOWING DETAILS AS REQUIRED BY THE FBC ACCESSIBILITY |
| | CODE. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |