Plan Review Notes
Plan Review Notes For Permit 23040064
Permit Number 23040064
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-18 09:02:151ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23040064
 5/18/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: TDH- SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS
 FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE
 PUMP FROM ITS PUMP CURVE AND THE SIMPLIFIED TOTAL
 DYNAMIC HEAD CALCULATION IS NO LONGER ALLOWED TO BE
 USED IN DETERMINING MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7- 2013 SECS. 4.4.9, 4.4.9.1.
  
 2) SUBMIT THE POOL PUMP CURVE. IDENTIFY ON THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS.
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  