| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38 |
| | SELECTED PRODUCTS & SYSTEM NO. UDL-2 ARE NOT APPROVED |
| | FOR USE WITH FL19320-R2. THE UNDERLAYMENT SYSTEM |
| | REQUIRES A 30/90 HOT MOP SYSTEM. PLEASE PROVIDE THE |
| | CORRECT PRODUCTS & SYSTEM NO. FROM TABLE 4B ALLOWABLE |
| | DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE |
| | ROOF APPLICATIONS. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. SECOND REQUEST. |
| | 2. SUBMITTED PRODUCT APPROVAL FL1654-R31 IS INCOMPLETE. |
| | PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION |
| | REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. FLORIDA DBPR PRODUCT APPROVAL FL1654-R31 |
| | SYSTEM NO. W-112 DO NOT MEET THE MINIMUM ZONE 3 DESIGN |
| | PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C |
| | AREAS. PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN |
| | PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY C/PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH |
| | AN APPROVED SYSTEM. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. SECOND |
| | REQUEST. |
| | 3. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| | 17-0405.19 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE |
| | A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED HIP & RIDGE METAL |
| | SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. (FL5372-R6) SECOND REQUEST. |
| | 4. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. SECOND REQUEST. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH/PICTURES AND INCLUDE ROOF SLOPE(S), MEAN |
| | ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| | DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |