2023-04-14 12:26:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL19320-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5259-R38 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5259-R38 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 7-14 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 7-14 ONLY.
 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38
 SELECTED PRODUCTS & SYSTEM NO. UDL-2 ARE NOT APPROVED
 FOR USE WITH FL19320-R2. THE UNDERLAYMENT SYSTEM
 REQUIRES A 30/90 HOT MOP SYSTEM. PLEASE PROVIDE THE
 CORRECT PRODUCTS & SYSTEM NO. FROM TABLE 4B ALLOWABLE
 DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE
 ROOF APPLICATIONS. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
 5. SUBMITTED PRODUCT APPROVAL FL1654-R31 IS INCOMPLETE.
 PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION
 REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. FLORIDA DBPR PRODUCT APPROVAL FL1654-R31
 SYSTEM NO. W-112 DO NOT MEET THE MINIMUM ZONE 3 DESIGN
 PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C
 AREAS. PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN
 PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY C/PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH
 AN APPROVED SYSTEM. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3.
 6. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 17-0405.19 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED HIP & RIDGE METAL
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. (FL5372-R6)
 7. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
 8. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT
 COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL
 AND CHAPTER 11 OF THE 2020 FBC-PLUMBING.
 9. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  