| 2023-05-02 10:38:09 | BUILDING RESTORATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A CONCRETE REPAIR MAP SHOWING THE |
| | LOCATIONS OF THE CONCRETE REPAIR. FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE LOCATIONS AND SIZES OF THE WINDOWS |
| | TO BE REPLACED. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS. FBC 107.2.1 |
| | |
| | 4) DRAWING S-00 REFERS TO ASCE 7-10 - SHOULD BE ASCE |
| | 7-16 PER FBC CHAPTER 35 |
| | |
| | 5) PLEASE PROVIDE THE DETAILS FOR THE NEW GUARD RAILS - |
| | FBC 107.2.1 |
| | |
| | 6) THRESHOLD BLDG. REQUIRED STATEMENT: FBC W.P.B. |
| | AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT, |
| | TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA |
| | STATUTES. |
| | |
| | 7) THE PROVIDED SIGNED AND SEALED DRAWINGS AND |
| | THRESHOLD FORM DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE |
| | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED |
| | TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |