| Notes |
| Date |
Text |
| 2023-04-26 14:55:36 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE THE UPSTREAM 600 AMP PANEL LOAD | | | CALCULATION AND PANEL SCHEDULE IN ACCORDANCE WITH NEC | | | 215.5 | | | 2) | | | 215.5 DIAGRAMS OF FEEDERS. | | | IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A | | | DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR | | | TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM | | | SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR | | | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL | | | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE | | | DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING | | | DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO | | | BE USED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|