| 2023-07-21 14:16:04 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-23031894 |
| | 7/21/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #8 & 10 |
| | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES FOR FURTHER CLARIFICATION. |
| | |
| | 8) FAILED. P2 & P4: REFER TO SEC. 607.1.1 FBC P |
| | TEMPERATURE LIMITING MEANS. THE THERMOSTAT CONTROLS ON |
| | THE WATER HEATERS CANNOT BE THE LIMITING DEVICES FOR |
| | HOT WATER DELIVERY. PLEASE PROVIDE A MASTER |
| | THERMOSTATIC MIXING VALVE AND DETAIL THE PIPING |
| | CONNECTIONS. |
| | |
| | PLEASE PROVIDE A MASTER THERMOSTATIC MIXING VALVE AT |
| | THE WATER HEATERS. |
| | |
| | 10) FAILED. P2 & P4: REFER TO SEC. AND TABLE C404.5.1 |
| | FBC ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER |
| | SUPPLY PIPES TO THE PUBLIC LAVATORIES ARE EXCEEDINGLY |
| | THE 2FT. MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER |
| | SOURCES. |
| | |
| | THE HW RECIRCULATION LINES MUST BE LOOPED DOWN AND |
| | CONNECT TO THE LAVATORY HW FIXTURE SUPPLY PIPES AT A |
| | POINT WITHIN 2 FT. OF THE FIXTURE SUPPLY PIPE |
| | TERMINATIONS AT THE LAVS. |
| | |
| | NEW COMMENT. |
| | |
| | 1) P-1 & P-4: PLEASE PROVIDE A FLOOR CLEANOUT (FCO) FOR |
| | THE GREASE WASTE LINE INSIDE THE SPACE AT A POINT WHERE |
| | IT WILL NOT EXCEED 100 FT. FROM THE CLEANOUT AT THE |
| | GREASE INTERCEPTOR- SEC. 708.1.1 FBC P. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |