Plan Review Notes
Plan Review Notes For Permit 23031894
Permit Number 23031894
Review Stop P
Sequence Number 2
Notes
Date Text
2023-07-21 14:16:042ND REVIEW FBC-2020 PLUMBING
 PERMIT-23031894
 7/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #8 & 10
 FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES FOR FURTHER CLARIFICATION.
  
 8) FAILED. P2 & P4: REFER TO SEC. 607.1.1 FBC P
 TEMPERATURE LIMITING MEANS. THE THERMOSTAT CONTROLS ON
 THE WATER HEATERS CANNOT BE THE LIMITING DEVICES FOR
 HOT WATER DELIVERY. PLEASE PROVIDE A MASTER
 THERMOSTATIC MIXING VALVE AND DETAIL THE PIPING
 CONNECTIONS.
  
 PLEASE PROVIDE A MASTER THERMOSTATIC MIXING VALVE AT
 THE WATER HEATERS.
  
 10) FAILED. P2 & P4: REFER TO SEC. AND TABLE C404.5.1
 FBC ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER
 SUPPLY PIPES TO THE PUBLIC LAVATORIES ARE EXCEEDINGLY
 THE 2FT. MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER
 SOURCES.
  
 THE HW RECIRCULATION LINES MUST BE LOOPED DOWN AND
 CONNECT TO THE LAVATORY HW FIXTURE SUPPLY PIPES AT A
 POINT WITHIN 2 FT. OF THE FIXTURE SUPPLY PIPE
 TERMINATIONS AT THE LAVS.
  
 NEW COMMENT.
  
 1) P-1 & P-4: PLEASE PROVIDE A FLOOR CLEANOUT (FCO) FOR
 THE GREASE WASTE LINE INSIDE THE SPACE AT A POINT WHERE
 IT WILL NOT EXCEED 100 FT. FROM THE CLEANOUT AT THE
 GREASE INTERCEPTOR- SEC. 708.1.1 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  