Plan Review Notes
Plan Review Notes For Permit 23031894
Permit Number 23031894
Review Stop G
Sequence Number 2
Notes
Date Text
2023-07-21 14:31:482ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 23031894
 7/21/2023
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1B AND #2
 FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES FOR CLARIFICATION.
  
 1) FAILED. SHEET P2 GAS RISER- SEC. 107.3.5.1.5 WPB.
  
 B) PROVIDE THE SIZES OF THE SUPPLY PIPES FROM THE
 MANIFOLDS TO THE WATER HEATERS AND COOKING APPLIANCES.
 BASED ON TABLE 402.4(2) FBC FG 1-INCH PIPES ARE
 REQUIRED FOR THE WATER HEATERS, AND 3/4-INCH PIPES ARE
 REQUIRED AT THE OVEN AND THE HOT PLATE.
  
 REVISION PERMIT #22120309 SHOWS A 2 PSI SYSTEM WITH A
 TOTAL LENGTH OF 245 FT. AT THE CAPPED POINT ADJACENT TO
 THE NEW RESTAURANT SPACE. THERE IS NO LOW-PRESSURE
 REGULATOR(S) SHOWN ON THE NEW RISER EITHER AT THE
 COOKING LINE OR AT EACH APPLIANCE- SEC. 410.2 FBC FG.
 PLEASE SHOW THE REGULATOR(S) AND SHOW THE VENT LINE RUN
 AND TERMINATION LOCATION UNLESS THE REGULATOR(S) IS/ARE
 THE VENT-LIMITING TYPE(S).
  
 2) FAILED. P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE
 SUPPLIED- SEC. 304.1 FBC FG.
  
 2ND REQUEST FOR COMBUSTION AIR CALCULATIONS FOR THE
 COOKING APPLIANCES. PLEASE NOTE THAT MAKEUP AIR FOR THE
 EXHAUST HOOD CANNOT BE USED TO SUPPLY COMBUSTION AIR-
 SEC. 304.9.1 FBC FG.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  