| 2023-07-21 14:31:48 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23031894 |
| | 7/21/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1B AND #2 |
| | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES FOR CLARIFICATION. |
| | |
| | 1) FAILED. SHEET P2 GAS RISER- SEC. 107.3.5.1.5 WPB. |
| | |
| | B) PROVIDE THE SIZES OF THE SUPPLY PIPES FROM THE |
| | MANIFOLDS TO THE WATER HEATERS AND COOKING APPLIANCES. |
| | BASED ON TABLE 402.4(2) FBC FG 1-INCH PIPES ARE |
| | REQUIRED FOR THE WATER HEATERS, AND 3/4-INCH PIPES ARE |
| | REQUIRED AT THE OVEN AND THE HOT PLATE. |
| | |
| | REVISION PERMIT #22120309 SHOWS A 2 PSI SYSTEM WITH A |
| | TOTAL LENGTH OF 245 FT. AT THE CAPPED POINT ADJACENT TO |
| | THE NEW RESTAURANT SPACE. THERE IS NO LOW-PRESSURE |
| | REGULATOR(S) SHOWN ON THE NEW RISER EITHER AT THE |
| | COOKING LINE OR AT EACH APPLIANCE- SEC. 410.2 FBC FG. |
| | PLEASE SHOW THE REGULATOR(S) AND SHOW THE VENT LINE RUN |
| | AND TERMINATION LOCATION UNLESS THE REGULATOR(S) IS/ARE |
| | THE VENT-LIMITING TYPE(S). |
| | |
| | 2) FAILED. P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| | THE COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE |
| | SUPPLIED- SEC. 304.1 FBC FG. |
| | |
| | 2ND REQUEST FOR COMBUSTION AIR CALCULATIONS FOR THE |
| | COOKING APPLIANCES. PLEASE NOTE THAT MAKEUP AIR FOR THE |
| | EXHAUST HOOD CANNOT BE USED TO SUPPLY COMBUSTION AIR- |
| | SEC. 304.9.1 FBC FG. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |