| 2023-04-19 15:42:34 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-23031894 |
| | 4/19/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE F |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-8.0: IN ACCORDANCE WITH TABLE 403.1 FBC P, A |
| | PUBLIC OCCUPANT LOAD OF 152 REQUIRES 2 MALE AND 2 |
| | FEMALE WATER CLOSETS. THE PLANS SHOWS A DEFICIENCY OF |
| | ONE MALE AND ONE FEMALE WATER CLOSET FOR PUBLIC USE. |
| | PLEASE REVISE THE PLANS TO SHOW COMPLIANCE. |
| | |
| | 2) A-11.0: PLEASE SHOW THE CLEAR FLOOR SPACE DIMENSIONS |
| | FOR THE WATER CLOSETS AND THE LAVATORIES- SECS. 604.3 & |
| | 606.2 FBC ACC. |
| | |
| | 3) A-11.0: PLEASE SHOW THE CENTERLINES OF THE TOILET |
| | PAPER DISPENSERS MEASURED FROM THE FRONTS OF THE WATER |
| | CLOSETS- SEC. AND FIGURE 604.7 FBC ACC. |
| | |
| | 4) P-1: A PERMIT APPLICATION FOR THE GREASE INTERCEPTOR |
| | IS REQUIRED TO BE SUBMITTED PRIOR TO THE MAIN PLUMBING |
| | PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION TBD (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | ([email protected]) AND I WILL CHANGE THE REVIEW STATUS TO |
| | PASS. |
| | |
| | 5) P-1: A COMPLETE REVIEW OF THE PLUMBING SYSTEMS |
| | CANNOT BE COMPLETED WITHOUT NUMBERED OR LETTERED |
| | PLUMBING FIXTURE AND EQUIPMENT SCHEDULES WITH |
| | CORRESPONDING NUMBERS OR LETTERS ON THE PLANS- SEC. |
| | 107.2.1 WPB. |
| | |
| | 6) P-1 & P4: THE PLAN AND RISER DRAWING APPEAR TO SHOW |
| | DRAINAGE FROM HAND SINKS AND FLOOR SINKS BELOW ICE |
| | MAKERS AND BINS DISCHARGING INTO THE GREASE WASTE LINE |
| | WHICH IS NOT ALLOWED PER SEC. 1003.3.1 FBC P. |
| | |
| | 7) P1 & P4: PLEASE NOTE THE GREASE INTERCEPTOR PERMIT |
| | 22060318 IS IN APPLICATION PHASE AND NO PLANS HAVE BEEN |
| | SUBMITTED FOR REVIEW. GREASE INTERCEPTOR SUBMITTAL |
| | REQUIREMENTS ARE AS FOLLOWS- |
| | A) CIVIL PLAN SHOWING THE INTERCEPTOR, PIPING, AND |
| | CLEANOUT LOCATIONS |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND |
| | CAPACITY OF THE UNIT. |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| | FOR GRAVITY TYPES. |
| | D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND |
| | SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL |
| | VENTS, AND SAMPLING PORTS. |
| | E) MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP BY |
| | THE ENGINEER OF RECORD- SECS.1003.3.5 OR 1003.3.7 FBC |
| | P. |
| | F) ACCESS LID SPECIFICATIONS INDICATING THE LIDS WILL |
| | BE EQUIPPED WITH ACCESS RESTRICTORS AND WILL BE HEAVY |
| | DUTY TRAFFIC RATED (WHERE REQUIRED). |
| | |
| | 8) P2 & P4: REFER TO SEC. 607.1.1 FBC P TEMPERATURE |
| | LIMITING MEANS. THE THERMOSTAT CONTROLS ON THE WATER |
| | HEATERS CANNOT BE THE LIMITING DEVICES FOR HOT WATER |
| | DELIVERY. PLEASE PROVIDE A MASTER THERMOSTATIC MIXING |
| | VALVE AND DETAIL THE PIPING CONNECTIONS. |
| | |
| | 9) P2 & P4: REFER TO SECS. 419.5 & 607.1.2 FBC P AND |
| | INDICATE THE MEANS OF PROVIDING TEMPERED WATER DELIVERY |
| | FROM THE PUBLIC LAVATORY SINKS. |
| | |
| | 10) P2 & P4: REFER TO SEC. AND TABLE C404.5.1 FBC |
| | ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER SUPPLY |
| | PIPES TO THE WATER HEATERS ARE EXCEEDINGLY THE 2FT. |
| | MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER SOURCES. |
| | IN ORDER TO CORRECT, THE RECIRCULATION LINES MUST BE |
| | DROPPED DOWN AND CONNECT WITHIN 2 FT. OF THE HW SUPPLY |
| | PIPE TERMINATIONS. |
| | |
| | 11) P2 & P4: SHOW THE LOCATIONS OF BACKFLOW PREVENTERS |
| | FOR SUPPLY PIPES TO THE DISHWASHER AND OTHER FIXTURES |
| | AND EQUIPMENT THAT COULD CAUSE CONTAMINATION OF THE |
| | POTABLE WATER SUPPLY- SEC. 608.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |