Plan Review Notes
Plan Review Notes For Permit 23031894
Permit Number 23031894
Review Stop P
Sequence Number 1
Notes
Date Text
2023-04-19 15:42:341ST REVIEW FBC-2020 PLUMBING
 PERMIT-23031894
 4/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE F
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-8.0: IN ACCORDANCE WITH TABLE 403.1 FBC P, A
 PUBLIC OCCUPANT LOAD OF 152 REQUIRES 2 MALE AND 2
 FEMALE WATER CLOSETS. THE PLANS SHOWS A DEFICIENCY OF
 ONE MALE AND ONE FEMALE WATER CLOSET FOR PUBLIC USE.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
  
 2) A-11.0: PLEASE SHOW THE CLEAR FLOOR SPACE DIMENSIONS
 FOR THE WATER CLOSETS AND THE LAVATORIES- SECS. 604.3 &
 606.2 FBC ACC.
  
 3) A-11.0: PLEASE SHOW THE CENTERLINES OF THE TOILET
 PAPER DISPENSERS MEASURED FROM THE FRONTS OF THE WATER
 CLOSETS- SEC. AND FIGURE 604.7 FBC ACC.
  
 4) P-1: A PERMIT APPLICATION FOR THE GREASE INTERCEPTOR
 IS REQUIRED TO BE SUBMITTED PRIOR TO THE MAIN PLUMBING
 PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 ([email protected]) AND I WILL CHANGE THE REVIEW STATUS TO
 PASS.
  
 5) P-1: A COMPLETE REVIEW OF THE PLUMBING SYSTEMS
 CANNOT BE COMPLETED WITHOUT NUMBERED OR LETTERED
 PLUMBING FIXTURE AND EQUIPMENT SCHEDULES WITH
 CORRESPONDING NUMBERS OR LETTERS ON THE PLANS- SEC.
 107.2.1 WPB.
  
 6) P-1 & P4: THE PLAN AND RISER DRAWING APPEAR TO SHOW
 DRAINAGE FROM HAND SINKS AND FLOOR SINKS BELOW ICE
 MAKERS AND BINS DISCHARGING INTO THE GREASE WASTE LINE
 WHICH IS NOT ALLOWED PER SEC. 1003.3.1 FBC P.
  
 7) P1 & P4: PLEASE NOTE THE GREASE INTERCEPTOR PERMIT
 22060318 IS IN APPLICATION PHASE AND NO PLANS HAVE BEEN
 SUBMITTED FOR REVIEW. GREASE INTERCEPTOR SUBMITTAL
 REQUIREMENTS ARE AS FOLLOWS-
 A) CIVIL PLAN SHOWING THE INTERCEPTOR, PIPING, AND
 CLEANOUT LOCATIONS
 B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND
 CAPACITY OF THE UNIT.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL
 VENTS, AND SAMPLING PORTS.
 E) MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP BY
 THE ENGINEER OF RECORD- SECS.1003.3.5 OR 1003.3.7 FBC
 P.
 F) ACCESS LID SPECIFICATIONS INDICATING THE LIDS WILL
 BE EQUIPPED WITH ACCESS RESTRICTORS AND WILL BE HEAVY
 DUTY TRAFFIC RATED (WHERE REQUIRED).
  
 8) P2 & P4: REFER TO SEC. 607.1.1 FBC P TEMPERATURE
 LIMITING MEANS. THE THERMOSTAT CONTROLS ON THE WATER
 HEATERS CANNOT BE THE LIMITING DEVICES FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A MASTER THERMOSTATIC MIXING
 VALVE AND DETAIL THE PIPING CONNECTIONS.
  
 9) P2 & P4: REFER TO SECS. 419.5 & 607.1.2 FBC P AND
 INDICATE THE MEANS OF PROVIDING TEMPERED WATER DELIVERY
 FROM THE PUBLIC LAVATORY SINKS.
  
 10) P2 & P4: REFER TO SEC. AND TABLE C404.5.1 FBC
 ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER SUPPLY
 PIPES TO THE WATER HEATERS ARE EXCEEDINGLY THE 2FT.
 MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER SOURCES.
 IN ORDER TO CORRECT, THE RECIRCULATION LINES MUST BE
 DROPPED DOWN AND CONNECT WITHIN 2 FT. OF THE HW SUPPLY
 PIPE TERMINATIONS.
  
 11) P2 & P4: SHOW THE LOCATIONS OF BACKFLOW PREVENTERS
 FOR SUPPLY PIPES TO THE DISHWASHER AND OTHER FIXTURES
 AND EQUIPMENT THAT COULD CAUSE CONTAMINATION OF THE
 POTABLE WATER SUPPLY- SEC. 608.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  