| 2023-04-26 06:34:30 | 1ST REVIEW FMC |
| | PERMIT: 23031894 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE COVER SHEET INDICATES THIS TO BE A PROPOSED |
| | OCCUPANCY OF A-2. WHAT IS THE CURRENT OCCUPANCY OF THIS |
| | SPACE? |
| | |
| | 2) PROVIDE A MECHANICAL DEMO PLAN FOR THIS PROJECT. FBC |
| | 107.3.5 |
| | |
| | 3) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT |
| | THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT |
| | WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | 4) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT |
| | REFRIGERATION EQUIPMENT WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION AND A SEPARATE REVIEW AS IT WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | 5) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | FOR THIS PROJECT. FEC C403.2.1 |
| | |
| | 6) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH SPACE |
| | IN THIS BUILDOUT ACCORDING TO THE OCCUPANCY |
| | CLASSIFICATION OF EACH SPACE AND THE OCCUPANT DENSITY |
| | FROM FMC TABLE 403.3.1.1 |
| | |
| | 7) SHOW THE VENTILATION AIR INTAKES ARE 10 FEET FROM |
| | THE LOT LINE AND STREET. FMC 401.3 AND 401.4 |
| | |
| | 8) VERIFY THAT THE RETURN AIR INTAKES IN THE KITCHEN |
| | ARE A MINIMUM OF 10 FEET FROM THE COOKING APPLIANCES. |
| | FMC 601.5 NUMBER 7. |
| | |
| | 9) SHOW THAT THE MECHANICAL SYSTEM WILL BE SIZED FOR |
| | THE LOAD OF THE WALK-IN COOLER AND FREEZER CONDENSING |
| | UNITS INSTALLED INSIDE THE KITCHEN CONDITIONED AREA. |
| | FEC C403.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |