| 2023-04-19 16:06:07 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23031894 |
| | 4/19/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2 GAS RISER- SEC. 107.3.5.1.5 WPB. |
| | |
| | A) PROVIDE THE PIPE SIZE AND LENGTH OF THE BRANCH LINE |
| | SUPPLYING THE WATER HEATERS. |
| | |
| | B) PROVIDE THE SIZES OF THE SUPPLY PIPES FROM THE |
| | MANIFOLDS TO THE WATER HEATERS AND COOKING APPLIANCES. |
| | BASED ON TABLE 402.4(2) FBC FG 1-INCH PIPES ARE |
| | REQUIRED FOR THE WATER HEATERS, AND 3/4-INCH PIPES ARE |
| | REQUIRED AT THE OVEN AND THE HOT PLATE. |
| | |
| | 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | WATER HEATER AND COOKING APPLIANCES AND INDICATE HOW |
| | THE AIR WILL BE SUPPLIED- SEC. 304.1 FBC FG. |
| | |
| | 3) P2: PROVIDE A COMPLETE VENTING DIAGRAM FOR THE WATER |
| | HEATERS BASED ON MANUFACTURER'S SPECIFICATIONS (SEC. |
| | 624.1) AND SECS. 503.6- 503.8 FBC FG. SHOW THE TYPE AND |
| | SIZE OF VENT FLUES, VENT FLUE RUN LENGTHS AND |
| | TERMINATION LOCATIONS WITH REQUIRED CLEARANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |