| 2023-04-03 12:39:40 | FIRE PROVISO: |
| | |
| | ALL ACCESS CONTROL SHALL COMPLY WITH REQUIREMENTS OF |
| | NFPA 101, CH 7, MEANS OF EGRESS. |
| | |
| | 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED |
| | EGRESS |
| | DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE |
| | PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL |
| | LOCKING SYSTEMS |
| | RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED |
| | THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF |
| | THE ELECTRICAL |
| | LOCK IS AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY |
| | OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING |
| | CONDITIONS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE |
| | DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE |
| | POWER SUPPLY TO |
| | THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION |
| | OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY ELECTRICALLY |
| | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | |
| | |
| | 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS. |
| | 7.2.1.6.1 DELAYED-EGRESS ELECTRICAL LOCKING SYSTEMS. |
| | 7.2.1.6.1.1 APPROVED, DELAYED-EGRESS ELECTRICAL LOCKING |
| | SYSTEMS SHALL |
| | BE PERMITTED TO BE INSTALLED ON DOOR ASSEMBLIES SERVING |
| | LOW- AND |
| | ORDINARY- |
| | HAZARD CONTENTS IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM |
| | IN ACCORDANCE WITH SECTION 9.7, AND WHERE PERMITTED IN |
| | CHAPTERS 11 |
| | THROUGH 43, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE DELAY OF THE DELAYED-EGRESS ELECTRICAL LOCKING |
| | SYSTEM SHALL |
| | DEACTIVATE ALLOWING UNOBSTRUCTED EGRESS UPON ACTUATION |
| | OF ONE OF |
| | THE FOLLOWING: |
| | (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.7 |
| | (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.6 |
| | (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.6 |
| | (2) THE DELAY OF THE DELAYED-EGRESS ELECTRICAL LOCKING |
| | SYSTEM SHALL |
| | DEACTIVATE ALLOWING UNOBSTRUCTED EGRESS UPON LOSS OF |
| | POWER CONTROLLING |
| | THE LOCK OR LOCKING MECHANISM. |
| | (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE |
| | ELECTRICAL LOCK IN THE |
| | DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 SECONDS |
| | WHERE |
| | APPROVED BY THE AUTHORITY HAVING JURISDICTION, UPON |
| | APPLICATION OF |
| | A FORCE TO THE RELEASE DEVICE REQUIRED IN 7.2.1.5.10 |
| | UNDER ALL OF THE |
| | FOLLOWING CONDITIONS: |
| | (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF |
| | (67 N). |
| | (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY |
| | APPLIED FOR |
| | MORE THAN 3 SECONDS. |
| | (C) THE INITIATION OF THE RELEASE PROCESS SHALL |
| | ACTIVATE AN AUDIBLE |
| | SIGNAL IN THE VICINITY OF THE DOOR OPENING. |
| | (D) ONCE THE ELECTRICAL LOCK HAS BEEN RELEASED BY THE |
| | APPLICATION |
| | OF FORCE TO THE RELEASING DEVICE, REARMING THE DELAY |
| | ELECTRONICS |
| | SHALL BE BY MANUAL MEANS ONLY. |
| | (4)* A READILY VISIBLE, DURABLE SIGN THAT CONFORMS TO |
| | THE VISUAL CHARACTERS |
| | REQUIREMENTS OF ICC/ANSI A117.1, ACCESSIBLE AND USABLE |
| | BUILDINGS |
| | AND FACILITIES, SHALL BE LOCATED ON THE DOOR LEAF |
| | ADJACENT TO THE |
| | RELEASE DEVICE IN THE DIRECTION OF EGRESS, AND SHALL |
| | READ AS FOLLOWS: |
| | (A) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED |
| | IN 15 SECONDS, FOR DOORS THAT SWING IN THE DIRECTION OF |
| | EGRESS TRAVEL |
| | (B) PULL UNTIL ALARM SOUNDS, DOOR CAN BE OPENED |
| | IN 15 SECONDS, FOR DOORS THAT SWING AGAINST THE |
| | DIRECTION |
| | OF EGRESS TRAVEL |
| | |