Plan Review Notes
Plan Review Notes For Permit 23031811
Permit Number 23031811
Review Stop M
Sequence Number 1
Notes
Date Text
2023-04-17 05:59:201ST REVIEW FMC
 PERMIT: 23031811
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW MECHANICAL SYSTEM IS
 CONDITIONING THE MASTER AREA AND THE NEW FAMILY ROOM.
 THE TV ROOM AND LAUNDRY AREA WAS CONVERTED FROM THE
 GARAGE. WHAT IS CONDITIONING THIS NEW SPACE? SHOW HOW
 THESE ARE TO BE CONDITIONED, SHOW THE DUCT WORK AND
 MECHANICAL SYSTEM TO BE USED. THE ENERGY CALCULATIONS
 AND MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOW 1048
 SQ.FT. THIS IS FOR THE ADDITION. THE GARAGE IS BEING
 CONVERTING TO LIVING SPACE. IS THIS NEWLY CONVERTED
 LIVING SPACE APART OF THE ENERGY CALCULATIONS? WHAT IS
 CONDITIONING THIS LIVING SPACE? IF THE EXISTING AHU IS
 BEING USED TO CONDITION THIS NEW LIVING SPACE PLEASE
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 AND DETAILS OF THE EXISTING UNIT TO VERIFY IT IS
 CAPABLE OF CONDITIONING THE ADDITION LOAD. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  