| 2023-04-10 08:20:00 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND - 105.1/107.3 --THE GREASE TRAP |
| | REQUIRES A SEPARATE PERMIT THAT IS REQUIRED TO BE |
| | APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. |
| | YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) |
| | IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO |
| | [email protected]. AFTER YOU HAVE THE PERMIT |
| | GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| | LETTER AND I WILL COMPLY THIS COMMENT. |
| | |
| | 2. 2020 FPC 708.1.1 AND 708.1.3 - DETAIL THE REQUIRED |
| | CLEANOUT AT INTERVALS NO MORE THAN 100 FEET ON THE |
| | BUILDING DRAINS AS WELL AS THE REQUIRED CLEANOUTS JUST |
| | OUTSIDE THE BUILDING AT THE JUNCTION OF THE BUILDING |
| | DRAIN AND THE BUILDING SEWER ON BOTH THE SANITARY AND |
| | THE GREASE WASTE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |