| Plan Review Notes For Permit 23031769 |
| Permit Number |
23031769 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-10 14:54:19 | CREATING SHELL SUITES | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS ALS1.1 AND ALS1.2 - UNDER "CODE DATA" SUITE | | | NUMBERS DO NOT MATCH FLOOR PLAN AND INCLUDE ONLY 3 | | | UNITS - PLEASE RE EVALUATE. | | | | | | 2) DRAWINGS ALS1.1 AND ALS1.2 - UNDER "OCCUPANCY LOAD" | | | THE OCCUPANT LOAD SHOULD MATCH THE INFO SHOWN UNDER | | | "CODE DATA" | | | | | | 3) DRAWING A-8.0.1 - DETAIL 6 - OR THE STRUCTURAL | | | DRAWINGS - PLEASE SHOW THE EXTERIOR WALL BOTTOM AND TOP | | | TRACK ATTACHMENTS, SHOW THE PLYWOOD ATTACHMENTS, SHOW | | | THE DENS DECK ATTACHMENTS ETC. FBC WPB 107.2.1 | | | | | | 4) DRAWING A-8.0.1 - DETAIL 6 - PLEASE SHOW THE | | | EXTERIOR WALL WATER RESISTIVE BARRIER - FBC 1404.2 | | | WATER-RESISTIVE BARRIER. | | | NOT FEWER THAN ONE LAYER OF NO.15 ASPHALT FELT, | | | COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR OTHER | | | APPROVED MATERIALS, SHALL BE ATTACHED TO THE STUDS OR | | | SHEATHING, WITH FLASHING AS DESCRIBED IN SECTION | | | 1405.4, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS | | | WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR WALL | | | VENEER. | | | | | | 5) PLEASE SHOW THE EXTERIOR WINDOW/DOOR FLASHING PER - | | | FBC 1405.4 |
|