| Plan Review Notes For Permit 23031763 |
| Permit Number |
23031763 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-14 11:36:52 | 1ST ROOFING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | 1. NOA 22-0103.12 MODIFIED BITUMEN | | | SYSTEM SELECTED ??? C (2) (PG. 19/47) | | | WOOD DECK/INSULATED | | | SYSTEM DESIGN PRESSURE (DP) -67.5 | | | BASE SHEET - MECHANICAL FASTENERS | | | MEAN ROOF HEIGHT ??? 30 FEET (TABLE R301.2(2) -89.4PSF | | | EXPOSURE ??? D (TABLE R301.2(3) ADJUSTMENT COEFFICIENT | | | X 1.66 | | | DESIGN PRESSURE ??? ZONE 3 (-148.4) DP -148.4 | | | GENERAL LIMITATIONS #7 SHALL APPLY. (PG. 47/47) | | | | | | 2. PROVIDE ENHANCED FASTENER CALCULATIONS FOR PERIMETER | | | AND CORNER AREAS. | | | CALCULATIONS SHALL BE PREPARED, SIGNED AND SEALED BY A | | | FLORIDA PROFESSIONAL ENGINEER, REGISTERED ARCHITECT OR | | | REGISTERD ROOF CONSULTANT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|