| 2023-04-26 12:47:07 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23031690 |
| | 4/26/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET CVR: THE AERIAL PHOTO AND VICINITY MAP |
| | LOCATION ARE FOR THE WRONG ADDRESS. PLEASE CORRECT- |
| | SEC. 107.2.1 WPB. |
| | |
| | 2) CVR: PLEASE CORRECT THE PLUMBING FIXTURE CALCULATION |
| | NOTE ADDRESSING SEPARATE FACILITIES IN ACCORDANCE WITH |
| | SEC. 403.2 FBC P- SEPARATE FACILITIES ARE NOT REQUIRED |
| | IN B OCCUPANCIES WITH AN OCCUPANT LOAD OF 15 OR FEWER. |
| | |
| | 3) A1 & A3: THE BATHROOM FLOOR PLAN AND FIXTURE LAYOUT |
| | SHOWN IN DETAIL 8/A3 DOES NOT MATCH THE LAYOUT SHOWN ON |
| | A1. PLEASE CORRECT- SEC. 107.2.1 WPB. |
| | |
| | 4) A3: SHOW THE GRAB BAR HEIGHT MEASUREMENTS FROM THE |
| | FINISHED FLOORS TO THE TOPS OF THE BARS- SEC. 609.4 FBC |
| | ACC. |
| | |
| | 5) A3: SHOW THE HEIGHT OF THE MIRROR MEASURED FROM THE |
| | FINISHED FLOOR TO THE REFLECTIVE SURFACE- SEC. 603.3 |
| | FBC ACC. |
| | |
| | 6) P-1: SHOW THE LOCATIONS OF REQUIRED CLEANOUTS AT THE |
| | JUNCTIONS OF THE 3-INCH AND 2-INCH BUILDING DRAINS AND |
| | THE BUILDING SEWER LINE- SEC. 708.1.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |