| 2023-04-26 16:46:40 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23031639 |
| | 4/26/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: PROVIDE A GAS RISER DRAWING IN ACCORDANCE |
| | WITH SEC. 107.3.5.3 WPB. THE RISER SHALL PROVIDE THE |
| | FOLLOWING ITEMS- |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | C) TYPES AND SIZES OF PIPING. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | G) OUTLET PRESSURES AT REGULATORS. |
| | H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | I) PIPE SIZING TABLES. |
| | |
| | 2) A-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE IN COMPLIANCE WITH SEC. G2407.1 FBC RES. IF USING |
| | THE STANDARD METHOD PER SEC. G2407.5.1 THE MINIMUM |
| | REQUIRED VOLUME SHALL BE 50 CU.FT. PER 1,000 BTUH. |
| | |
| | 3) A-1: THE LOCATION OF THE GAS DRYER IN THE BATHROOM |
| | CLOSET IS ALLOWED ONLY IF IT MEETS SEC. G2406.2 ITEM 5- |
| | THE CLOSET DOOR SHALL BE A SOLID WEATHER-STRIPPED DOOR |
| | EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE. ALL |
| | COMBUSTION AIR SHALL BE TAKEN DIRECTLY FROM THE |
| | OUTDOORS IN USING PERMANENT OPENINGS DESIGNED |
| | ACCORDANCE WITH SECTION G2407.6. BECAUSE THERE ARE |
| | ADJACENT STORAGE ROOMS OUTSIDE OF THE LAUNDRY CLOSET |
| | ITEM 6 UNDER SEC. G2406.2 WOULD NOT APPLY. |
| | |
| | 4) E-1: THE PLAN SHOWS A SYMBOL FOR A STORAGE-TYPE GAS |
| | WATER HEATER ON THE EXTERIOR OF THE BUILDING. STORAGE |
| | TYPE WATER HEATERS ARE TYPICALLY DESIGNED FOR INDOOR |
| | USE OR WOULD HAVE TO BE IN A WEATHERPROOF ENCLOSURE ON |
| | THE EXTERIOR- SEC. G2448.1. IS THE INTENTION TO INSTALL |
| | A TANKLESS-TYPE WATER HEATER? PLEASE CLARIFY AND SHOW |
| | THE HEATER LOCATION ON A-1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |