| Date |
Text |
| 2023-05-02 17:55:01 | RESIDENTIAL (R2)BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23031597 |
| | 2621 VILLAGE BLVD # 405 |
| | |
| | 1- CLEARLY SPECIFY TYPE OF FINISH FLOORING TO BE |
| | INSTALLED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2-FLOORING SOUND INSULATION MATERIAL: |
| | (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 AND 720.2 OF FBC |
| | 7TH EDITION (2020). |
| | |
| | (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| | (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| | FLOOR FINISH. |
| | NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| | OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| | SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| | |
| | NOTE: |
| | SOUND INSULATION TEST FOR A CONCRETE SLAB WITH A |
| | SUSPENDED ACOUSTICAL CEILING WILL NOT BE APPROVED |
| | UNLESS APPLICANT PROVIDES PROOF OF ACOUSTICAL CEILING |
| | IN AREAS TO HAVE THE NEW FLOORING. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |