2023-04-04 05:53:21IT APPEARS THAT AN AV CLOSET WAS ADDED TO THIS NEW
 REVISED DRAWING. THERE IS A NEW 4 INCH DUCT IN THIS AV
 CLOSET. THIS NEW 4 INCH DUCT COMES FROM THE RETURN BOX
 IN THE HALL. PLEASE REMOVE THIS RETURN FROM THE AV
 CLOSET. FRC M1602.2 NUMBER 4. IF EXCEPTION NUMBER 4 IS
 USED PROVIDE THE INFORMATION REQUIRED BY EXCEPTION
 NUMBER 4 ON THE MECHANICAL DRAWING.
  