2023-06-01 09:21:29PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [DISTANCES TO PROPERTY LINES AND BUILDINGS WAS NOT
 SPECIFIED.] SUBMIT A SURVEY. SHOW THE LOCATION OF THE
 PROPOSED GENERATOR. SPECIFY THE DISTANCE TO PROPERTY
 LINES AND BUILDINGS. FBC AMENDMENTS 107.2.1
  
 2) [NOT RESOLVED.] THE GENERATOR EXHAUST IS REQUIRED TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 3) [NOT RESOLVED.] THE PROPOSED GENERATOR IS LOCATED IN
 A SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND
 EQUIPMENT IS REQUIRED TO BE LOCATED AT OR ABOVE THE
 LIVING SPACE OF THE DWELLING. SHOW COMPLIANCE, FBC-
 R322.1.6
  
 4) SUBMIT A RESPONSE LETTER SPECIFYING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  