| Plan Review Notes For Permit 23031581 |
| Permit Number |
23031581 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-01 09:21:29 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [DISTANCES TO PROPERTY LINES AND BUILDINGS WAS NOT | | | SPECIFIED.] SUBMIT A SURVEY. SHOW THE LOCATION OF THE | | | PROPOSED GENERATOR. SPECIFY THE DISTANCE TO PROPERTY | | | LINES AND BUILDINGS. FBC AMENDMENTS 107.2.1 | | | | | | 2) [NOT RESOLVED.] THE GENERATOR EXHAUST IS REQUIRED TO | | | BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 3) [NOT RESOLVED.] THE PROPOSED GENERATOR IS LOCATED IN | | | A SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND | | | EQUIPMENT IS REQUIRED TO BE LOCATED AT OR ABOVE THE | | | LIVING SPACE OF THE DWELLING. SHOW COMPLIANCE, FBC- | | | R322.1.6 | | | | | | 4) SUBMIT A RESPONSE LETTER SPECIFYING HOW EACH OF THE | | | REVIEW COMMENTS HAS BEEN ADDRESSED. | | | |
|