Plan Review Notes
Plan Review Notes For Permit 23031581
Permit Number 23031581
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-14 11:42:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SURVEY. SHOW THE LOCATION OF THE PROPOSED
 GENERATOR. SPECIFY THE DISTANCE TO PROPERTY LINES AND
 BUILDINGS. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 3) THE PROPOSED GENERATOR IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. THE GENERATOR AND EQUIPMENT IS REQUIRED TO
 BE LOCATED AT OR ABOVE THE LIVING SPACE OF THE
 DWELLING. SHOW COMPLIANCE, FBC- R322.1.6
  