| 2023-03-29 13:49:18 | 1ST REVIEW FMC |
| | PERMIT: 22080521 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A0.4 INDICATES THE WALLS IN THE LOBBY ARE 1 |
| | HOUR RATED. SHEET M1.2 DOES NOT HAVE THE REQUIRED FIRE |
| | DAMPERS WHERE THE MAIN TRUNK LINE PENETRATES THESE |
| | WALLS. PLEASE SHOW THE REQUIRED FIRE DAMPERS AT THESE |
| | PENETRATIONS. FMC 607.5.3 |
| | |
| | 2) PLEASE REFRESH MY MEMORY, THERE ARE 3 SYMBOLS IN THE |
| | EXIT PASSAGEWAY CEILING. WHAT ARE THESE SYMBOLS? WHY |
| | ARE THEY IN THE RATED CEILING OF THIS EXIT PASSAGEWAY? |
| | |
| | 3) SHEET A0.4 INDICATES THE WALLS SEPARATING THE TENANT |
| | SPACES FROM THE CORRIDOR ARE ALSO 1 HOUR RATED WALLS. |
| | PLEASE PROVIDE THE FIRE DAMPERS REQUIRED FOR THE |
| | PENETRATIONS IN THESE WALLS. FMC 607.5.3 |
| | |
| | 4) SHOW ON SHEET M1.2 THAT THE VAV???S WILL BE SHUT |
| | DOWN IN THE CASE OF SMOKE. FMC 606.2.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |