Plan Review Notes
Plan Review Notes For Permit 23031547
Permit Number 23031547
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-18 10:25:59PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) WPB AMENDMENTS TO FBC B 109.3, THE VALUATION
 APPEARS TO BE TOO LOW PER THE MARSHALL/SWIFT VALUATIONS
 RANGE. IT APPEARS THAT THE VALUE FOR THIS PROJECT
 SHOULD BE MORE THAN TWICE AS MUCH AS INDICATED IN THIS
 APPLICATION. PLEASE RE-EVALUATE AND RESUBMIT VALUATION.
  
 2.) FBC B 107.2.1, THE SUBMITTED APPLICATION INDICATES
 THAT THIS IS FOR A HARDWOOD FLOOR INSTALLATION BUT THE
 SUBMITTED COPY OF THE CONTRACT ESTIMATE INDICATES THIS
 IS FOR VINYL FLOORING. PLEASE CLARIFY THE TYPE OF
 FLOORING THAT IS PROPOSED.
  
 3.) FBC B 107.2.1, THERE IS NO INDICATION OF THE TYPE
 OF FLOORING UNDERLAYMENT THAT IS INTENDED TO BE USED
 FOR SOUND PROOFING AND FLAME SPREAD.
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
2023-04-17 10:17:35THE CONTRACT INDICATES VINYL FLOORING TO BE INSTALLED.
 PROVIDE TESTING DOCUMENTATION FOR THE FIRE PERFORMANCE
 OF THE MATERIALS TO BE INSTALLED TO INCLUDE THE
 CRITICAL RADIANT FLUX OF THE MATERIALS. NFPA 101,
 10.2.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  