| Plan Review Notes For Permit 23031541 |
| Permit Number |
23031541 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-04 13:59:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF FLOOR BARRIERS INSTALLTIONS | | | THAT APPEAR TO INVLOVE THE MEANS OF EGRESS, TRAVEL PATH | | | AND/OR FLOOR/THRESHOLD LEVELS. | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS | | | | | | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE | | | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. | | | | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A DETAILED | | | REVIEW OF THE AFFECTED MEANS OF EGRESS IN COMPLIANCE | | | WITH NFPA 101, CH 7, MEANS OF EGRESS REQUIREMENTS. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|