Plan Review Notes
Plan Review Notes For Permit 23031541
Permit Number 23031541
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-04-04 13:59:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOOR BARRIERS INSTALLTIONS
 THAT APPEAR TO INVLOVE THE MEANS OF EGRESS, TRAVEL PATH
 AND/OR FLOOR/THRESHOLD LEVELS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A DETAILED
 REVIEW OF THE AFFECTED MEANS OF EGRESS IN COMPLIANCE
 WITH NFPA 101, CH 7, MEANS OF EGRESS REQUIREMENTS.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  