| 2023-04-05 09:41:01 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND - 105.1/107.3 - THERE ISN'T A |
| | CORRESPONDING GENERATOR PERMIT. WHEN THE GENERATOR |
| | PERMIT IS APPLIED FOR, I CAN COMPLY THIS COMMENT. THE |
| | PLACEMENT OF THE GAS LINE IS RELATIVE TO THE SEPARATION |
| | DISTANCES REQUIRED AND REVIEWED IN THE GENERATOR PERMIT |
| | REVIEWS. |
| | |
| | 2. 2017 WPB AMEND 107.3.5.3 (13) - PROVIDE A FLOOR PLAN |
| | THAT OVERLAYS THE GAS ROUTING WITH RESPECT TO THE FLOOR |
| | PLAN. SHOW LOCATIONS OF THE FIXTURES WITHIN THE FLOOR |
| | PLAN. |
| | |
| | 3. 2017 WPB AMEND 107.3.5.3 (13) - INCLUDE ROOM SIZING |
| | AND COMBUSTION AIR CALCS FOR THE FIREPLACE AND RANGE. |
| | |
| | 4. 2017 WPB AMEND 107.3.5.3 (13) - ON THE FLOOR PLAN, |
| | INCLUDE SEPARATION FROM STRUCTURE OPENINGS. GENERATORS |
| | ARE 10 FEET FROM OPENINGS, POOL HEATERS ARE 4 FEET FROM |
| | OPENINGS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |