Plan Review Notes
Plan Review Notes For Permit 23031402
Permit Number 23031402
Review Stop B
Sequence Number 3
Notes
Date Text
2023-04-28 10:30:31JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN
 REVISED TO FL10497-R10. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-4 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3. THIRD REQUEST.
 2. SUBMITTED MIAMI-DADE COUNTY NOA 20-0714.01 COVERS
 MULTIPLE PRODUCTS & APPROVED ASSEMBLIES: SYSTEMS E(1)
 THROUGH E(4). SELECT PRODUCT & SYSTEM TO BE USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SECOND
 REQUEST. CANNOT BE INSTALLED DIRECT-TO-DECK. SECOND
 REQUEST
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE. THIRD REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  