| 2023-05-12 09:20:11 | 2ND PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. THE DETAIL STILL HAS THE WORDS "NATURAL GAS FIRED |
| | INTANT HOT WATER HEATER" RIGHT ON THE WATER HEATER. |
| | 2017 WPB AMENDS 107.2.1 - THE PLANS SHOW THE DETAIL FOR |
| | AN "ELECTRIC INSTANT HOT WATER HEATER" AND THE DETAIL |
| | ABOVE THAT TITLE SAYS "NATURAL GAS FIRED..." PLEASE FIX |
| | |
| | 2. ALL HOT WATER MUST GO THROUGH A MIXING VALVE. PER |
| | THIS SECTION, THE THERMOSTAT CANNOT BE THE LIMITING |
| | DEVICE FOR ANY HOT WATER DELIVERY. IF YOU WANT 110 AND |
| | 150 DEGREE WATER, YOU WILL NEED TWO MIXING VALVES. |
| | 2020 FPC 607.1.1/613.1 - HOT WATER DELIVERY - PER THIS |
| | SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT |
| | SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER |
| | DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE. |
| | THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE |
| | INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1. |
| | THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC |
| | HANDWASHING PROTECTION FOR TEMPERED WATER |
| | |
| | 3. PUBLIC HAND WASHING HAS A DIFFERENT REQUIREMENT AND |
| | NEEDS A 1070 DEVICE INSTALLED AT THE PUBLIC SINK. A |
| | DETAIL FOR THE PUBLIC SINK HAS NOT BEEN ADDED. |
| | 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND SHOW |
| | COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR PUBLIC |
| | HANDWASHING FACILITIES AND TEMPERED WATER. THE DEVICE |
| | SHOULD CONFORM TO ASSE 1070. |
| | |
| | 4. NOT ADDRESSED. |
| | 2017 WPB AMENDS 107.2.1 - PER THE CODE CASE PICTURES, |
| | THERE IS A WATER LINE NOT SHOWN ON THE PLANS. THE |
| | PICTURES SHOW A WATER LINE DIRECTLY ACROSS THE ROOM |
| | FROM THE PASTA BOILER. |
| | |
| | 5. THE CODE CASE SHOWS "NEW" CPVC LINES. YOU HAVE NOW |
| | REMOVED THE NOTE FOR CPVC AND LABELED THEM AS EXISTING. |
| | THE WATER LINES WERE DESCRIBED AS NEW BY THE |
| | CONTRACTOR. THEY CANNOT BE LABELED AS EXISTING AS THEY |
| | NEED TO BE INSPECTED. |
| | 2017 WPB AMENDS 107.2.1 - PER THE CODE CASE PICTURES, |
| | THERE IS NEW CPVC LINES INSTALLED. THE PLANS INDICATE |
| | "ALL NEW C.W. PIPING COPPER". PLEASE ADDRESS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |