| Date |
Text |
| 2023-03-29 07:31:12 | WEST PALM BEACH DEVELOPMENT SERVICES- |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23031364 |
| | ADD: 400 CLEMATIS ST. # 103 |
| | CONT: R. C. COLE CONSTRUCTION |
| | TEL: 561-523-7245 |
| | E-MAIL: BOBCOLE@RCCONSTRUCTIONINC |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 29TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION VALUE IS LOW FOR THE AMOUNT |
| | OF WORK BEING COMPLETED UNDER THIS PERMIT. |
| | 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) SHEET A3.03 WALL AND CABINETRY DETAILS SHOW A NEW |
| | DINING COUNTER IN THE FRONT WINDOW MARKED C AND IS AT A |
| | HEIGHT OF 36 INCHES. THE PLANS DO NOT STATE THE AMOUNT |
| | OF SEATS AND TABLE SPACES THERE IS IN THE DINING ROOM |
| | PLEASE PROVIDE COMPLIANCE FOR THE |
| | FOLLOWINGACCESSIBILITY CODE REQUIREMENTS, THE SHEET |
| | A3.03 DOES NOT SHOW COMPLIANCE WITH THE 2020 |
| | FBC-ACCESSIBILITY CODE. |
| | |
| | 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, BARS, INCLUDING RAISED |
| | OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 2D) 902.1. DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| | PROVISIONS, EMPLOYEE WORKSTATIONS. |
| | |
| | 2E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3) SHEET A3.03 SHOWS BOTH COUNTER HEIGHTS COUNTER C AT |
| | 36 INCHES IN HEITH AND COUNTER TYPE D AT 30 INCHES OF |
| | HEIGTH. AS STATED ABOVE IN COMMENT 2E)(2) ) 902.3 |
| | HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 INCHES |
| | MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. PLEASE ALSO SHOW POINT OF SALE COUNTER ON THE |
| | FLOOR PLAN. |
| | |
| | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |