2023-04-06 10:10:37FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE.
 NEC 220
 2. PROVIDE PANEL SCHEDULE SHOWING THE FOLLOWING
 INFORMATION:
 A. PANEL RATING WITH PROTECTION (MAIN BREAKER) RATING
 B. PANEL SCHEDULE SHOWING NEW EQUIMENT INSTALLED
 NEC 408.4(A)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  