| 2023-03-28 16:37:57 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23031345 |
| | ADD: 529 S FLAGLER DR # 28E |
| | CONT: CAMBRIDGE CONSTRUCTION LLC |
| | TEL: 561-784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 28/2023 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-100: |
| | 1A) NOTE # 7 STATES NEW 5/8-INCH DRYWALL OVER ??-INCH |
| | PLYWOOD WITH BATT INSULATION IN 2X4 OR 2X6 STUD SPACE. |
| | PLEASE NOTE THIS IS A HIGHRISE BUILDING, IF WOOD IS TO |
| | BE USED WITHIN WALL CAVITIES. PLEASE REVIEW IN THE 2020 |
| | FBC-BUILDING SECTION 603.1. FIRE RETARDANT TREATED WOOD |
| | SHALL BE PERMITTED IN: |
| | 603.1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | |
| | 1B) NOTE # 10 STATES INSTALL NEW WOOD FLOORS OVER |
| | PROFLEX SUPER SIM 90 ACOUSTIC MEMBRANE TO MATCH |
| | EXISTING. PLEASE NOTE DOCUMENTS SUBMITTED ARE WHISPER |
| | MAT CS FOR SOUND AND FLAME SPREAD NOT PROFLEX SUPER SIM |
| | 90. BOTH PRODUCT WERE TEST FOR CERAMIC OR PORCELAIN |
| | TILE NOT FOR WOOD FLOORS. PROFLEX MAKES A PRODUCT THAT |
| | IS TESTED FOR WOOD LAMINATE FLOORING STC 50 AND IIC 54 |
| | WITH FLAME SPREAD TESTING. |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 1B)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 1B)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 1B)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | OR |
| | 1B)(3) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR |
| | LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT |
| | SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE COC FF-1 -PILL TEST (CPSC |
| | 16 CFR PART 1630) OR WITH ASTM D2859. |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253. |
| | |
| | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |