| Plan Review Notes For Permit 23031324 |
| Permit Number |
23031324 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-24 08:28:09 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | OPENINGS 13, 14, 15, & 17 OF THE SHUTTER SCHEDULE ARE | | | SHOWING 6" AND 9" ANCHOR SPACING FOR THE C-4 | | | CONNECTIONS. THESE CONNECTIONS (PER THE INDICATIONS | | | MARKED IN PRODUCT APPROVAL FL 17080-R3 SHEET #13 OF 13) | | | SHOULD BE AT 3"O.C.. | | | | | | PLEASE CORRECT THE OPENING SCHEDULE. |
|