| Plan Review Notes For Permit 23031282 |
| Permit Number |
23031282 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-24 15:00:13 | 1ST REVIEW FMC | | | PERMIT: 23031282 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET D-101 AND D-102 ARE MISSING FROM THIS | | | SUBMITTAL. SHEET M-01 INDICATES THAT AHU-1 AND AHU-2 | | | ARE NEW. ARE THESE NEW SYSTEMS AS IN THERE WERE NO | | | MECHANICAL SYSTEMS IN THESE AREAS BEFORE OR NEW AS IN | | | REPLACEMENT UNITS? IF THEY ARE REPLACEMENT UNITS ARE | | | THEY LIKE FOR LIKE REPLACEMENTS? IF SO, PLEASE PROVIDE | | | THE LIKE FOR LIKE CHANGE OUT FORMS FOR EACH UNIT. FEC | | | R403.7 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|