Plan Review Notes
Plan Review Notes For Permit 23031274
Permit Number 23031274
Review Stop THRESHOLD
Sequence Number 1
Notes
Date Text
2023-05-09 09:28:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MAY 09TH/ 2023
 ACTION: DENIED
 1)3RD REQUEST. DIGITAL SEAL WILL NOT OPEN FOR
 VERIFICATION FOR PLANS S-1, S-2 & S-3 , THRESHOLD
 INSPECTION PLAN AND PROJECT MANUAL UPLOADED 4/6/23. THE
 DIGITAL SIGNATURE DOES NOT OPEN FOR 3RD PARTY
 VERIFICATION. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) PLANS IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE'S
 SIGNATURE SHALL NOT BE USED ON ELECTRONIC/DIGITALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) SEMI-COMPLIED, THRESHOLD INSPECTION PLAN DIGITAL
 SIGNATURE WILL NOT OPEN FOR THIRD PARTY VERIFICATION.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
 1) ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C., MAY BE SIGNED
 DIGITALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE. AS USED HEREIN, THE
 TERMS "CERTIFICATION AUTHORITY"? AND "DIGITAL
 SIGNATURE" SHALL HAVE THE MEANINGS ASCRIBED TO THEM IN
 SECTIONS 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS
 INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED.
  
  
 3B) SEMI-COMPLIED PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN, DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE.
 JOHNATHAN GIL REGISTRATION NOT FILED IN AS AN ENGINEER
 NOR INSPECTOR BN LICENSE. NOTE THE STATE SHOWS THERE
 ARE 2 JOHNATHAN GIL???S AS INTERNS. STATE STATUTE 468
 PART XII OF THE STATE OF FLORIDA AND SECTION 110.8.6
 FLORIDA BUILDING CODE.
  
 3C) 3RD REQUEST. RESPONSE STATES THIS STATEMENT ADDED
 TO SHEET S-1. THERE ARE NO REVISION DATES SHOWN ON
 SHEET S1, NEITHER IS THERE DELTAS OR CLOUDED AREA WHERE
 THIS STATEMENT HAS BEEN ADDED.
 THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) SEMI-COMPLIED. FOR THE SPECIAL INSPECTOR. NOT
 JOBSITE INSPECTORS WITH EITHER ENGINEERS LICENSE, OR BN
 INSPECTORS LICENSE. THE BUILDING OFFICIAL OR HIS
 DESIGNEE WILL REVIEW THE RESUME'. AFTER THE RESUME' IS
 REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 3E) 3RD REQUEST. RESPONSE CONTRACTOR WILL PROVIDE. THE
 CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION. NOT THIS REVIEW CYCLE.
  
 4) 3RD REQUEST. WITHIN THE DOCUMENTS SUBMITTED THE
 JOBSITE INSPECTOR IS AN ENGINEER INTERN, DOES THE
 INTERN HOLD A STATE BN INSPECTOR LICENSE. THE RESPONSE
 LETTER STATES THAT YOU ARE MEETING THE STATE STATUTES,
 YES UNDER THE ENGINEERING STATUTE BUT NOT UNDER OUR
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE
  
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  