| 2023-04-11 15:57:54 | ADDING LAUNDRY ROOM |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) SHOW WALL FRAMING TO BE FIRE RETARDANT- FBC 602.3 |
| | TYPE III. |
| | TYPE III CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN |
| | WHICH THE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE |
| | MATERIALS AND THE INTERIOR BUILDING ELEMENTS ARE OF ANY |
| | MATERIAL PERMITTED BY THIS CODE. FIRE-RETARDANT-TREATED |
| | WOOD FRAMING COMPLYING WITH SECTION 2303.2 SHALL BE |
| | PERMITTED WITHIN EXTERIOR WALL ASSEMBLIES OF A 2-HOUR |
| | RATING OR LESS. |
| | |
| | 2) PLEASE SHOW THE 2HR EXTERIOR FIRE RATED WALL |
| | ASSEMBLY - FBC 703.3 METHODS FOR DETERMINING FIRE |
| | RESISTANCE. |
| | |
| | 3) FBC 705.5 FIRE-RESISTANCE RATINGS. |
| | EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN |
| | ACCORDANCE WITH TABLES 601 AND 602 AND THIS SECTION. |
| | THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR WALLS |
| | WITH A FIRE SEPARATION DISTANCE OF GREATER THAN 10 FEET |
| | (3048 MM) SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE |
| | INSIDE. THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR |
| | WALLS WITH A FIRE SEPARATION DISTANCE OF LESS THAN OR |
| | EQUAL TO 10 FEET (3048 MM) SHALL BE RATED FOR EXPOSURE |
| | TO FIRE FROM BOTH SIDES. |
| | |
| | 4) PLEASE SHOW THE BUILDING SET BACKS FROM THE PROPERTY |
| | LINES. |
| | |
| | 5) PLEASE SHOW THE EAVE OVERHANG DISTANCE FROM THE |
| | PROPERTY LINES - SEE FBC TABLE 705.2 MINIMUM DISTANCE |
| | OF PROJECTION |
| | |
| | 6) PLEASE SHOW THE EXTERIOR WALL SHEATHING ATTACHMENTS |
| | - TYPE, SIZE AND ON CENTER SPACING - FBC WPB 107.2.1 |
| | |
| | 7) PLEASE SHOW THE EXTERIOR WALL -WATER RESISTIVE |
| | BARRIER - FBC 1404.2 WATER-RESISTIVE BARRIER. |
| | NOT FEWER THAN ONE LAYER OF NO.15 ASPHALT FELT, |
| | COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR OTHER |
| | APPROVED MATERIALS, SHALL BE ATTACHED TO THE STUDS OR |
| | SHEATHING, WITH FLASHING AS DESCRIBED IN SECTION |
| | 1405.4, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS |
| | WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR WALL |
| | VENEER. |
| | |
| | 8) PLEASE SHOW THE EXTERIOR WALL STRAPPING FROM THE |
| | BOTTOM PLATE TO THE ROOF RAFTERS - FBC 1604.8.1 |
| | GENERAL. |
| | ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF |
| | WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO |
| | RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM |
| | THE APPLICATION OF THE PRESCRIBED LOADS. |
| | |
| | 9) PLEASE SHOW THE ROOF RAFTER ATTACHMENT TO THE |
| | EXISTING STRUCTURE - FBC 1604.8.1 |
| | |
| | 10) THE DRAWINGS SHOW ROOF INSULATION AS R 30 BATTS - R |
| | 30 BATT INSULATION WILL NOT FIT IN A 2X4 ROOF RAFTERS. |
| | - FBC 1203.2 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND |
| | BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH |
| | THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1 |
| | INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION |
| | AND THE ROOF SHEATHING. |
| | |
| | 11) DRAWINGS SHOW A STAIR WITH A 9 INCH TREAD DEPTH |
| | WHICH DOES NOT COMPLY WITH - FBC 1011.5.2 - ACCESSORY |
| | TO INDIVIDUAL DWELLING UNITS IN GROUP R-2 OCCUPANCIES; |
| | THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (197 MM); |
| | THE MINIMUM TREAD DEPTH SHALL BE 10 INCHES |
| | |
| | 12) PLEASE SHOW THE STAIR RISER HEIGHT - FBC 1011.5.2 |
| | |
| | 13) PLEASE SHOW THE REQUIRED STAIR HANDRAILS - FBC |
| | 1011.11 |
| | |
| | 14) SPRINKLERS ARE REQUIRED FOR THE ADDED LAUNDRY ROOMS |
| | - SINCE THE WINDOWS ARE BETWEEN THE LIVING SPACE AND |
| | THE LAUNDRY ROOM - THE FIRE AREA FOR THE UNIT IS BEING |
| | INCREASED - FBC EXISTING BUILDING 1102.3 FIRE |
| | PROTECTION SYSTEMS. EXISTING FIRE AREAS INCREASED BY |
| | THE ADDITION SHALL COMPLY WITH CHAPTER 9 OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | FBC SECTION 201 - FIRE AREA. THE AGGREGATE FLOOR AREA |
| | ENCLOSED AND BOUNDED BY FIRE WALLS, FIRE BARRIERS, |
| | EXTERIOR WALLS OR HORIZONTAL ASSEMBLIES OF A BUILDING. |
| | |
| | 15) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS |
| | AND ROOFING SYSTEMS. ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD IF NOT LISTED BY THE PRODUCT APPROVAL NUMBER |
| | ON THE DRAWINGS. FBC WPB 107.3.4 |
| | |
| | 16) ALL OF THE SIGNED AND SEALED DRAWINGS DO NOT SHOW |
| | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |