| 2023-03-21 10:12:12 | FIRE PROVISO COMMENT: | | | | | | TO ENSURE THE AUDIBLE SIGNALS ARE CLEARLY HEARD, THEY | | | SHALL HAVE A SOUND LEVEL OF AT LEAST 15DB ABOVE THE | | | AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM | | | SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, | | | WHICHEVER IS GREATER, MEASURED 5 FT. ABOVE THE FLOOR IN | | | THE AREA REQUIRED TO BE SERVED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|