Plan Review Notes
Plan Review Notes For Permit 23031235
Permit Number 23031235
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-21 10:12:12FIRE PROVISO COMMENT:
  
 TO ENSURE THE AUDIBLE SIGNALS ARE CLEARLY HEARD, THEY
 SHALL HAVE A SOUND LEVEL OF AT LEAST 15DB ABOVE THE
 AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM
 SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS,
 WHICHEVER IS GREATER, MEASURED 5 FT. ABOVE THE FLOOR IN
 THE AREA REQUIRED TO BE SERVED.
  