| Date |
Text |
| 2023-04-03 17:26:44 | WEST PALM BEACH DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23031230 |
| | ADD: 525 S FLAGLER DR UNIT 22A & 22B |
| | CONT: ALBRIGHT CONSTRUCTION |
| | TEL: 561-547-7433 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 03/2023 |
| | ACTION: DENIED NOTEE PICTURE SUBMITTED THROUGH E-MAIL |
| | SHOWING THE LOCATION OF THE EXISTING DRAIN. SHANE |
| | SCHANS ALBRIGHT 561-644-1674. |
| | |
| | 1) THE PLANS ARE SILENT AS TO THE EXISTING DRAIN PIPE |
| | AND WHERE IT WAS CAPPED, WILL THERE BE ANY NEW |
| | PENETRATIONS THROUGH THE FLOOR SLAB. POST TENSION SLAB/ |
| | NEW HOLES. THE PLAN IS SILENT AS IF THE LOCATION OF THE |
| | EXISTING TUB DRAIN IS GOING TO BE REUSED IN THE SAME |
| | LOCATION. IF NOT, THEN THE FLOOR SLAB WILL NEED TO BE |
| | X-RAYED TO FIND THE POST TENSION CHORD LOCATIONS. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| | FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| | WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |