| Plan Review Notes For Permit 23031204 |
| Permit Number |
23031204 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-14 15:17:32 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23031204 | | | 4/14/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A & P PLANS: A DRINKING FOUNTAIN IS A REQUIRED | | | FIXTURE FOR BUSINESS OCCUPANCIES PER TABLE 403.1 FBC P. | | | WHERE DRINKING FOUNTAINS ARE REQUIRED A MINIMUM OF TWO | | | SHALL BE PROVIDED- ONE HI AND ONE LO. PLEASE REVISE THE | | | PLANS TO SHOW THE FIXTURE LOCATIONS AND PLUMBING PIPING | | | REQUIREMENTS. | | | A) REFER TO SECS. 602.1- 602.7 FBC ACC AND PROVIDE | | | ACCESSIBILITY COMPLIANCE DETAILS ON THE PLANS FOR THE | | | DRINKING FOUNTAINS- CLEAR FLOOR SPACES, KNEE AND TOE | | | CLEARANCES, SPOUT HEIGHTS. | | | | | | 2) A101 & A401: PLEASE PROVIDE ACCESSIBILITY COMPLIANCE | | | DETAILS FOR THE NEW EXAM AND LAB SINKS PER SECS. 212.3, | | | 606.2, AND 606.3 FBC ACC. | | | | | | 3) A402: PROVIDE A DETAIL SHOWING THE KNEE AND TOE | | | CLEARANCES FOR THE ACCESSIBLE LAVATORIES- SEC. 606.2 | | | FBC ACC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|