| Plan Review Notes For Permit 23031204 |
| Permit Number |
23031204 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-24 11:20:22 | 1ST REVIEW FMC | | | PERMIT: 23031204 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE ADD THE TENANT SPACE UNIT NUMBERS THAT WILL | | | BE AFFECTED WITH THIS EXPANSION AND IMPROVEMENT | | | APPLICATION. | | | | | | 2) SHEET M111: KEYNOTE 7- THE REQUIRED SMOKE DETECTOR | | | MUST BE INSTALLED ON THE SUPPLY SIDE OF THE MECHANICAL | | | SYSTEM. FMC 606.2.1 | | | | | | 3) SHEET M111: KEYNOTE 3 MENTIONS BIOHAZARD AREAS. | | | PLEASE IDENTIFY THE BIOHAZARD AREAS ON THIS DRAWING AND | | | SHOW THE EXHAUST FANS FOR THESE SPACES. FMC 510 | | | | | | 4) SHOW THE EXHAUST FANS AND EXHAUST DUCT FOR ALL | | | BATHROOM EXHAUSTS. FBC 107.3.5 | | | | | | 5) SHEET M111: PLEASE SHOW THE RETURN AIR PATH FROM | | | ROOM PFT 141 BACK TO THE AHU. FMC 601.6 | | | | | | 6) SHEET M111: SHOW THE RETURN AIR PATH FROM THE | | | PHYSICIAN???S STATION BACK TO AHU-3. FMC 601.6 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|