2023-04-24 11:20:221ST REVIEW FMC
 PERMIT: 23031204
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD THE TENANT SPACE UNIT NUMBERS THAT WILL
 BE AFFECTED WITH THIS EXPANSION AND IMPROVEMENT
 APPLICATION.
  
 2) SHEET M111: KEYNOTE 7- THE REQUIRED SMOKE DETECTOR
 MUST BE INSTALLED ON THE SUPPLY SIDE OF THE MECHANICAL
 SYSTEM. FMC 606.2.1
  
 3) SHEET M111: KEYNOTE 3 MENTIONS BIOHAZARD AREAS.
 PLEASE IDENTIFY THE BIOHAZARD AREAS ON THIS DRAWING AND
 SHOW THE EXHAUST FANS FOR THESE SPACES. FMC 510
  
 4) SHOW THE EXHAUST FANS AND EXHAUST DUCT FOR ALL
 BATHROOM EXHAUSTS. FBC 107.3.5
  
 5) SHEET M111: PLEASE SHOW THE RETURN AIR PATH FROM
 ROOM PFT 141 BACK TO THE AHU. FMC 601.6
  
 6) SHEET M111: SHOW THE RETURN AIR PATH FROM THE
 PHYSICIAN???S STATION BACK TO AHU-3. FMC 601.6
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  