| Plan Review Notes For Permit 23031203 |
| Permit Number |
23031203 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-21 11:14:26 | INTUMESCENT PAINT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE BUILDING DESIGNER OF RECORD HAS MARKED THE | | | SUBMITTAL AS "MAKE CORRECTIONS" - YOU WILL NEED TO MAKE | | | THE CORRECTIONS AND SUBMIT A PACKAGE THAT IS MARKED "NO | | | EXCEPTION TAKEN". "ARCHITECT NEEDS TO VERIFY THE | | | THICKNESS MEETS THE REQUIRED FIRE RATING" | | | | | | 2) PROVIDE A SIGNED AND SEALED DRAWING FROM THE | | | ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH | | | COLUMN AND THE INTUMESCENT PAINT THICKNESS. | | | | | | 3) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS. |
|