| 2023-03-24 15:23:03 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23031192 |
| | 3/24/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE- 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GREASE INTERCEPTOR: PROVIDE THE FOLLOWING |
| | INFORMATION ON THE PLAN PER SEC. 1003.3.5 FBC P. |
| | A) MAKE AND MODEL AND CAPACITY FOR THE INTERCEPTOR. |
| | B) GREASE WASTE CALCULATIONS. |
| | |
| | 2) ISOMETRIC DRAWING: IDENTIFY THE TYPE OF INDIRECT |
| | WASTE RECEPTOR SHOWN IN THE DRAWING. IT APPEARS TO BE A |
| | FLOOR SINK- SECS. 414.1 & 802.1 FBC P. |
| | |
| | 3) ISOMETRIC: SHOW THE SIZE OF THE UNDERSLAB WASTE PIPE |
| | FROM THE FLOOR SINK TO THE INTERCEPTOR. A MINIMUM |
| | 2-INCH DRAIN PIPE IS REQUIRED- TABLE 709.1 FBC P. |
| | |
| | 4) ISOMETRIC: THE AAV CANNOT BE USED TO VENT THE GREASE |
| | INTERCEPTOR PER SEC. 918.8 FBC P AND ARE TYPICALLY NOT |
| | APPROVED PER MANUFACTURER'S GUIDELINES. PROVIDE A VENT |
| | PIPE FOR THE SYSTEM THAT EXTENDS TO A VENT HEADER OR TO |
| | THE EXTERIOR OF THE BUILDING. |
| | |
| | 5) ISOMETRIC: PLEASE REFER TO THE MANUFACTURER'S |
| | INSTALLATION GUIDELINES CONCERNING THE FLOW CONTROL |
| | DEVICE. THE DEVICE MAY REQUIRE AN AIR INTAKE PIPE SEC. |
| | 1003.3.5 FBC P. |
| | |
| | 6) ISOMETRIC: PLEASE PROVIDE A WATER RISER AND SHOW THE |
| | SOURCE OF THE HOT WATER TO THE SINK- SEC. 107.3.5.1.3 |
| | WPB, AND SEC. 607.1 FBC P. |
| | |
| | 7) PLEASE PROVIDE A BASIC FLOOR DRAWING SHOWING THE |
| | PROPOSED LOCATION OF THE SINK AND GREASE INTERCEPTOR- |
| | SEC. 107.2.1 WPB. |
| | |
| | 8) PROVIDE A COMPLETE SCOPE OF WORK FOR THE NEW |
| | CATERING BUSINESS AND SUBMIT ADDITIONAL PLANS AND |
| | DETAILS FOR BUILDING DEPARTMENT REVIEW- SEC. 107.2.1 |
| | WPB. |
| | |
| | 9) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR OR |
| | QUALIFIER SHALL BE ON THE DRAWING- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |