| Plan Review Notes For Permit 23031183 |
| Permit Number |
23031183 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-17 11:02:15 | FIRE PROVISO: | | | | | | THE PROPOSED TRAILER IS TOO CLOSE TO THE PROPOSED | | | BUILDING PER NFPA 241, AND REQUIRES FIRE SPRINKLER | | | PROTECTION. | | | | | | PER NFPA 241, WITH A 64' WIDTH OF EXPOSURE, THE TRAILER | | | IS REQUIRED TO BE AT LEAST 50' AWAY FROM THE BUILDING. | | | | | | FIRE SPRINKLERS WILL PROVIDE FOR A 75% REDUCTION. | | | | | | HOWEVER, THE INSTALLATION OF ABC DRY CHEMICAL | | | SPRINKLERS PER MANUFACTURERS RECOMMENDATIONS WILL BE | | | CONSIDERED IN LIEU OF WET FIRE SPRINKLERS. | | | | | | PLEASE ENSURE THEY ARE INSTALLED. | | | | | | CONTACT MY OFFICE SHOULD YOU HAVE ANY QUESTIONS OR | | | CONCERNS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|