Plan Review Notes
Plan Review Notes For Permit 23031074
Permit Number 23031074
Review Stop P
Sequence Number 2
Notes
Date Text
2023-06-16 09:27:282ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT 23031074
 6/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SANITARY DRAINAGE AND VENT RISER
 DRAWING SHOWS NON-COMPLIANT WET VENTING FOR THE NEW
 BATHROOM FIXTURES. THE CURRENT DRAWING SHOWS NO VENTING
 FOR THE TOILET AND SHOWER. PLEASE REFER TO SEC. P3108.1
 & P3108.2.1 FBC RES. IN ORDER TO FIX THE SYSTEM, THE
 KITCHEN SINK FIXTURE DRAIN SHALL CONNECT TO THE 3-INCH
 BRANCH AT A POINT DOWNSTREAM OF THE BATHROOM FIXTURE
 DRAIN CONNECTIONS, AND THE LAV SINK DRAIN SHALL CONNECT
 TO THE 3-INCH AT A POINT UPSTREAM OF THE TOILET AND
 SHOWER FIXTURE DRAIN CONNECTIONS OR IN BETWEEN THE TWO.
  
 2) 2ND REQUEST. IT APPEARS TWO DWELLING UNITS WILL BE
 ON THE SAME LOT WHICH WILL REQUIRE WATER USERS TO
 INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF
 DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL
 BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST
 PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION
 CONTROL PROGRAM. PLEASE PLACE A NOTE ON THE PLAN
 ACCORDINGLY- SEC. 107.2.1 WPB.
  
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR AN RPZ
 BACKFLOW PREVENTION DEVICE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  