| 2023-06-16 09:27:28 | 2ND REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT 23031074 |
| | 6/16/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: THE SANITARY DRAINAGE AND VENT RISER |
| | DRAWING SHOWS NON-COMPLIANT WET VENTING FOR THE NEW |
| | BATHROOM FIXTURES. THE CURRENT DRAWING SHOWS NO VENTING |
| | FOR THE TOILET AND SHOWER. PLEASE REFER TO SEC. P3108.1 |
| | & P3108.2.1 FBC RES. IN ORDER TO FIX THE SYSTEM, THE |
| | KITCHEN SINK FIXTURE DRAIN SHALL CONNECT TO THE 3-INCH |
| | BRANCH AT A POINT DOWNSTREAM OF THE BATHROOM FIXTURE |
| | DRAIN CONNECTIONS, AND THE LAV SINK DRAIN SHALL CONNECT |
| | TO THE 3-INCH AT A POINT UPSTREAM OF THE TOILET AND |
| | SHOWER FIXTURE DRAIN CONNECTIONS OR IN BETWEEN THE TWO. |
| | |
| | 2) 2ND REQUEST. IT APPEARS TWO DWELLING UNITS WILL BE |
| | ON THE SAME LOT WHICH WILL REQUIRE WATER USERS TO |
| | INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF |
| | DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL |
| | BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST |
| | PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION |
| | CONTROL PROGRAM. PLEASE PLACE A NOTE ON THE PLAN |
| | ACCORDINGLY- SEC. 107.2.1 WPB. |
| | |
| | PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR AN RPZ |
| | BACKFLOW PREVENTION DEVICE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |