Plan Review Notes
Plan Review Notes For Permit 23031069
Permit Number 23031069
Review Stop M
Sequence Number 2
Notes
Date Text
2023-03-23 09:28:522ND REVIEW FMC
 PERMIT: 23031069
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE PREVIOUS REVIEW COMMENT BELOW. THIS
 REVIEWER PULLED UP THE MASTER TO TRY AND APPROVE THE
 WALK-IN COOLER PERMIT BUT I AM UNABLE TO FIND THE
 LOCATION OF THE WALK-IN COOLER CONDENSING UNIT. UNTIL
 THIS IS PROVIDED I CANNOT APPROVE THIS REVIEW. NOTE
 THAT IF IT IS ON THE ROOF AS STATED ON SHEET A1-4
 EQUIPMENT SCHEDULE A TIE DOWN METHOD MUST BE SUBMITTED.
  
 2) PROVIDE THE LOCATION OF THE CONDENSING UNIT FOR THE
 WALK-IN COOLER. IF IT IS TO BE MOUNTED ON THE ROOF
 PROVIDE ANCHORING DETAILS AND A ROOF DRAWING SHOWING
 THE LOCATION OF THIS CONDENSING UNIT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  