Plan Review Notes
Plan Review Notes For Permit 23031069
Permit Number 23031069
Review Stop M
Sequence Number 1
Notes
Date Text
2023-03-20 14:12:251ST REVIEW FMC
 PERMIT: 23031069
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE WALK-IN COOLER PACKAGE. THIS
 SHOULD INCLUDE THE REFRIGERATION DETAILS OF THIS
 WALK-IN COOLER. PROVIDE THE REFRIGERATION SPECS FOR
 THIS COOLER. FMC 1102.
  
 2) PROVIDE THE LOCATION OF THE CONDENSING UNIT FOR THE
 WALK-IN COOLER. IF IT IS TO BE MOUNTED ON THE ROOF
 PROVIDE ANCHORING DETAILS AND A ROOF DRAWING SHOWING
 THE LOCATION OF THIS CONDENSING UNIT. FBC 107.3.5
  
 3) THE DRAWING SUBMITTED FOR THE COOLER WALLS MUST
 INCLUDE THE DESIGNERS DIGITAL SIGNATURE. FS 471/481
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  