Plan Review Notes
Plan Review Notes For Permit 23031068
Permit Number 23031068
Review Stop G
Sequence Number 1
Notes
Date Text
2023-03-20 08:27:541ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23031068
 3/20/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS FLOOR PLAN: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE NEW GAS RANGE AND DRYER- SEC. G2407.1 FBC RES.
 REFER TO SEC. G2407.5.1 FOR STANDARD METHOD WHICH
 REQUIRES 50 CU. FT. PER 100 BTU'S. REFER TO EXCEPTION 1
 FOR ALTERNATE MAKEUP AIR ALLOWANCE FOR THE DRYER.
  
 2) GAS FLOOR PLAN: THE WATER HEATER EXHAUST OUTLET
 SHALL BE A MINIMUM OF 4 FT. FROM AIR INTAKE OPENINGS
 INTO THE BUILDING INCLUDING OPERABLE WINDOWS AND
 VENTILATION SOFFITS- G2427.8 & G2448.1 FBC RES. PLEASE
 SHOW THE OUTLET CLEARANCE TO THE BATHROOM WINDOW.
  
 3) THE PRINTED AND AND SIGNATURE OF THE CONTRACTOR OR
 QUALIFIER SHALL BE ON THE GAS RISER AND FLOOR PLAN
 DRAWINGS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  