Plan Review Notes
Plan Review Notes For Permit 23031040
Permit Number 23031040
Review Stop G
Sequence Number 1
Notes
Date Text
2023-03-20 16:38:59 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23031040
 3/20/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: PLEASE NOTE A SEPARATE PERMIT IS REQUIRED
 FOR THE GENERATOR HOWEVER THE 1-INCH SUPPLY PIPE TO THE
 UNIT MAY BE UNDERSIZED BASED ON THE APPROVED GAS PLAN
 WHICH SHOWS A 1,651,000 BTU GENERATOR. BASED ON TABLE
 G2413.4(1) FBC RES. THE 1-INCH SCHEDULE 40 SUPPLY PIPE
 TO THE 500 BTU GENERATOR IS ADEQUATE (MAX 678 BTU). THE
 ??-INCH SUPPLY PIPE TO THE POOL HEATER SHALL BE
 INCREASED TO 1-INCH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  